C-TEC's tried and trusted XFP two loop 32 zone addressable fire alarm panel - now available with C-TEC's own digital fire alarm system protocol, CAST and fully certified to EN54 parts 2, 4 & 13.

 

With two powerful 40V 450mA loop drivers allowing the connection of up to 255 CAST devices per loop, the installation of a robust, feature-packed addressable fire alarm system has never been easier.

 

Always thought of the XFP as an entry-level fire panel? Think again. Thanks to CAST's multiple type codes, high speed data transmission and two speedy soft addressing options (automatic via the panel or manually via a handheld programmer/device tester), it is undoubtedly one of the most powerful two loop fire panels around. This, and its ability to sit on a network of up to 8 XFP master panels, makes it ideal for use in small to medium sized stand-alone applications and larger, more sophisticated installations alike.

XFP Networkable Two Loop 32 Zone Control Panel (Apollo)

SKU: XFP502/X
    • Certified to EN54-2/4 by the Loss Prevention Certification Board (LPCB) and EN54-13 by Kiwa Telefication.
    • Two independently programmable conventional sounder circuits.
    • Two programmable inputs.
    • A fault output relay and three programmable relay outputs with voltage free changeover contacts.
    • A selection of zone dependency/coincidence functions.
    • A day/night (building occupied/unoccupied) function.
    • An investigation delay period function.
    • Phased evacuation facility.
    • An alarm counter that records how many times the panel has been in alarm state.
    • Powerful short circuit protected loop drivers.
    • An integral EN54-4/A2 switch mode.
    • Adjustable contamination levels.
    • Earth fault monitoring.
    • Combined keypad / keyswitch entry to Access Levels 2 and 3.
    • 500 event monitoring.
    • An intuitive Windows based upload-download PC program.
    • Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 non-redundant network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.
!